WAVE RIDER II (3-15 KW)
FEATURES
CSA Listed to UL 924, UL1778
3 and 5 kW in one cabinet
10, 12.5, & 15 kW one inverter and only one battery cabinet
Battery management system
Battery exerciser
True no break power to the load
LCD panel for monitoring of continuous self diagnostic
Seismic rated with bracket kit.
RS 232 & RS 485
90% Efficiency
Pulse width modulated (PWM) generator compatible
Sinusoidal wave
Incandescent, Fluorescent, HID, HPS
Power factor & energy efficient ballast.
Global Monitoring System Option
SPECIFICATIONS
Power Rating: 3, 5, 7.5, 10, 12.5, and 15 KW
Input Voltage: 3 & 5KW ....120, 208, 240, or 277 VAC
(-20% to +15%)
7.5, 10, 12.5, & 15kW ...... 208, 240 or
277VAC (-15% to +15%)
Output Voltage: 120 Volt Only, or 277 Volt with
external Isolation Transformer Only
Output Frequency: (Inverter Operation): 60Hz +0.5Hz.
Output Voltage Reg.: +3% Regulated within CBEMA curve
Output Wave Form: Sine-wave
Input Protection: Input circuit breaker
provided protection to the unit, load and
personnel. Input Circuit Breaker will be
higher interruption rated 42 (KAIC)
breaker as standard.
Output Protection: Internal Electronic overload
protection. Circuit breaker provides
inherent over-load protection.
Factory selectable voltage 120, 208, 240,
or 277 for input or output voltages. If
input is different from output or output
different from input, an internally
mounted transformer is required.
Serge Protection: The inverter will protect
itself and the load against surge as
defined in ANSI/IEEE C62.45 category A and B.
Power Factor: 1.0
Isolation: Output is completely isolated
from input, and with multi voltages, when input
& output is different.
Noise Isolation: -120 dB. Common-Mode.
60 dB. Transverse-Mode
Efficiency: 90% minimum
Crest Factor: 3.1 Typical (may vary by model)
Battery: Sealed maintenance free
Battery Mngmnt System: Utilizes a microprocessor
technology to monitor the batteries critical levels
and apply charging cycles in a method to substantially
increase battery life.
Housing: Free standing NEMA 1 Enclosure Power
coated paint Front access only Multiple conduit
entries Refer to chart for dimensions
Recharge Time: Approx. 16 times discharge rate
Environmental: Humidity: 0-95% RH w/no
condensation Operating temperature:
UPS: 0°C to +40°C. (-32°F to 102°F)
Battery: 20°C to +30°C. (68°F to 86°F)
Storage temperature: -20 to 60C.
Safety Agencies: CSA Listed to UL924, UL924A, & UL1778
|