VANDAL RESISTANT EMERGENCY LIGHT WITH BATTERY BACKUP
Download TES-VDR Vandal Resistant Emergency Light Cut Sheet
PRODUCT OVERVIEW
The TES-VDR series of emergency lighting units are constructed
from durable and secure polycarbonate and 18 gauge steel.
The VDR has been designed with the PulseGuard pulse
switching charger. The PulseGuard offers superior performance
and energy efficiency versus conventional constant voltage
chargers. Single or double 10 watt halogen lamps can be
ordered. Tamper resistant hardware is standard.
EXTERNAL SPECIFICATIONS
The TES-VDR series is constructed with an 18 gauge steel housing
and impact resistant polycarbonate diffuser. White powder coat
finish is standard (other colors optional). Internal emergency
light source available configured with single or double 10 watt
halogen lamps. Conduit knockouts are located on (3) three
sides and the back of each unit. External test switch and
monitor LED are standard.
MECHANICAL SPECIFICATIONS
The TES-VDR is constructed with a durable 18 gauge steel housing
and impact, corrosion and flame resistant polycarbonate
diffuser. Stamped conduit knockouts are located on (3) three
sides and the back of the TES-VDR unit. The TES-VDR is supplied
standard in a durable white powder coat, baked finish. Other
colors are available, including custom color matching, please
specify. External test switch and monitor LED are standard.
CHARGER SPECIFICATIONS
The TES-VDR series utilizes a pulse switching charger that is up to
70% more efficient than traditional constant voltage chargers.
The charger is a fully automatic current limited charger with
solid state line-latched low voltage disconnect protection. All
components used in the circuitry are temperature compensated.
The charger also has brownout and short circuit protection.
Charger status is easily determined via a dual diagnostic
LED display which indicates AC/ON and High Charge. An
external push button test switch allows maintenance personnel
to quickly determine the operational status of the unit and
lamp load.
LAMPHEAD FEATURES
The TES-VDR series is normally supplied with (1) one or (2) two
internally mounted 10 watt halogen lamps. Please specify the
lamp configuration required when ordering.
BATTERY TECHNOLOGY
The TES-VDR series is designed with a maintenance free, sealed
valve regulated lead acid battery that provides a minimum
emergency duration of 90 minutes (for the listed rating).
Recharge time of the battery is twenty-four (24) hours. The maximum working temperature is 50 C.
INSTALLATION
The TES-VDR emergency luminaire is suitable for surface wall or
ceiling mounting. Suitable for indoor and damp installations
on normally inflammable surfaces.
AUTO TEST
The TES-VDR auto-test feature automatically monitors the functional
operation of the unit. Auto-test monitors the operation of the
lamps, battery and circuitry and displays any alerts. Periodic
emergency tests, up to ninety (90) minutes duration are
simulated to ensure proper operation during an actual power
failure. Operating status is visually indicated by multi-function
LED indication.
WARRANTY
The TES-VDR comes from the factory with an unconditional 5 year
product warranty. Lamps are not covered.