Home :
Cast Aluminum Heavy Duty Wet/Damp Location, Vandal Resistant Exit
|
| |
|
|
Quantity in Basket:
None
Code: TES-TL
Price: $214.20
Shipping Weight: 8.00 pounds
|
| |
|
WET/DAMP LOCATION, VANDAL RESISTANT EXIT
CAST ALUMINUM/POLYCARBONATE CSONSTRUCTION
PRODUCT OVERVIEW
The Exit Stores TL wet location and harsh
environment exit combines rugged construction
and appealing aesthetics. Durable cast aluminum
and polycarbonate housing construction, standard
vandal resistant/anti-corrosion coated hardware and
Intelli-Charge electronics ensures long lasting
reliability even in the most severe environments.
The TL is UL listed for use in wet/damp
location applications ranging from -40°F (-40°C) to
113°F (45°C). Tuff-Act exits are shipped with
field-selectable chevrons, and can be ordered as a
single face or universal (single/double) face
configuration. Three color choices are available
and stencils may be ordered to match or in an
attractively contrasting brushed aluminum finish.
ILLUMINATION
Illumination of the exit stencil face is
accomplished with long lasting, high output Light
Emitting Diodes (LEDs). Hot spots and striations
are eliminated by the internal light chamber, which
is specially designed around the high performance
LED array. Average illumination levels are in
excess of 25fl (79 cd/m2).
HOUSING
Die-cast aluminum housing with premium impact-resistant
injection molded polycarbonate covers.
Housing is powder coated and back cover is molded in color
to match. Front cover is clear.
Stencil is provided with field selectable chevrons and is
contained inside the fully gasketed housing.
All exposed hardware is both vandal resistant and anticorrosion
coated.
Universal knockouts on backplate allow wall mounting
directly to standard junction boxes.
Die-cast aluminum canopy is provided for top/side mounting
and is powder coated to match housing.
Two knockouts are located on the frame to accommodate 1/2”
flex or rigid conduit.
ELECTRONICS
AC Only - 120/277 VAC dual voltage input with surge
protection is standard on all models.
Self-Powered - Charging system is microprocessor driven
with software embedded diagnostic routine and temperature
compensation. See specification sheet C1465 for electronics
details.
120/277 VAC input, surge protection, brownout, AC lockout
and low voltage disconnect features are standard.
SELF-DIAGNOSTICS
The Intelli-Charge diagnostic/charging platform with selftesting
mode automatically runs a one-minute self-test every
30 days and a 30-minute test on the sixth and twelfth month.
A one-minute or 90-minute test may be initiated via the push
to test switch on the unit or by activating the appropriate test
command on the optional IR test device.
BATTERY
Maintenance-free, sealed nickel cadmium battery
Supplies 120 minutes of emergency power
Estimated service life of 10 years
Operating temperature range of -40°F (-40°C) to 113°F (45°C)
Compliant with IEC 61951-1
CODE COMPLIANCE
UL 924 listed
UL damp and wet location listing -40°F (-40°C) to
113°F (45°C)
NFPA, UL, IBC, NEC, BOCA and OSHA illumination
standard
Energy Star compliant
Meets ADA specifications for wall mounted lighting
fixtures
IEC 61951-1 Life Testing (batteries)
WARRANTY
Five-year full electronics warranty.
Five-year full plus five-year prorated battery warranty.
ELECTRICAL SPECIFICATIONS
AC Only Operation - Input Power Requirements
Red – 3.8 watts (120 VAC), PF = 0.96
3.8 watts (277 VAC), PF = 0.91
Green – 4.0 watts (120 VAC), PF = 0.95
4.0 watts (277 VAC), PF = 0.90
Self-Powered - Input Power Requirements
Red – 4.7 watts (120 VAC), PF = 0.95
4.8 watts (277 VAC), PF = 0.97
Green – 4.7 watts (120 VAC), PF = 0.95
4.7 watts (277 VAC), PF = 0.99
|
|